Domain 1: Safety Practices 15% of exam

Question 1

A project specification requires a horizontal copper cabling system capable of supporting 10GBASE-T over the full 100-meter (328-foot) channel. What is the LOWEST cabling category that meets this requirement?

  1. Category 5e
  2. Category 6
  3. Category 6A
  4. Category 8
Show answer & explanation

Correct answer: C - Category 6A

Domain 2: Structured Cabling Fundamentals 20% of exam

Question 2

An installer is sizing a conduit that will contain four communications cables. According to the National Electrical Code, what is the maximum allowable conduit fill?

  1. 31%
  2. 40%
  3. 53%
  4. 60%
Show answer & explanation

Correct answer: B - 40%

Domain 3: Copper Cable Installation 20% of exam

Question 3

Before pulling a single 4-pair UTP cable, an installer checks the maximum pulling tension so the cable is not stretched in a way that degrades transmission performance. That maximum tension is:

  1. 110 N (25 lbf)
  2. 45 N (10 lbf)
  3. 220 N (50 lbf)
  4. 445 N (100 lbf)
Show answer & explanation

Correct answer: A - 110 N (25 lbf)

Domain 4: Termination and Connectorization 20% of exam

Question 4

An installer is terminating an 8-position (8P8C) modular plug using the T568B wiring scheme. Which colors terminate on pins 1 and 2, respectively?

  1. White/Green and Green
  2. White/Orange and Orange
  3. White/Blue and Blue
  4. White/Brown and Brown
Show answer & explanation

Correct answer: B - White/Orange and Orange

Domain 5: Testing and Troubleshooting 15% of exam

Question 5

A technician must splice a single-mode fiber backbone where minimizing insertion loss and back reflection is the top priority. Compared with a mechanical splice, a fusion splice generally provides:

  1. Higher loss but quicker and simpler to install in the field
  2. Equivalent loss using index-matching gel
  3. Lower cost with no specialized equipment
  4. Lower insertion loss and lower reflectance
Show answer & explanation

Correct answer: D - Lower insertion loss and lower reflectance

Domain 6: Documentation and Standards Compliance 10% of exam

Question 6

A field tester is configured to certify the permanent link of a horizontal copper run. Which component is NOT included in the permanent link measurement?

  1. The fixed horizontal cable
  2. The telecommunications outlet
  3. The equipment cords
  4. The patch-panel connection
Show answer & explanation

Correct answer: C - The equipment cords

More BICSI practice questions

Question 7

A newly installed Category 6 link passes the wire map test, but the certification tester reports a NEXT (near-end crosstalk) failure. The MOST likely cause is:

  1. A short between two conductors
  2. An open conductor on one pair
  3. A split pair
  4. A reversed pair
Show answer & explanation

Correct answer: C - A split pair

Question 8

During a retrofit, an installer finds communications cable above an accessible ceiling that is not connected to any equipment and is not tagged for future use. According to the NEC, this cable must be:

  1. Labeled and left in place
  2. Capped and left in the pathway
  3. Coiled and secured above the ceiling
  4. Removed from accessible areas
Show answer & explanation

Correct answer: D - Removed from accessible areas

Question 9

As the number of cables carrying Power over Ethernet (PoE) within a single bundle increases, an installer must manage one effect in particular. The primary concern that may require reducing the bundle size or derating is:

  1. Heat buildup within the cable bundle
  2. Increased alien crosstalk between cables
  3. Greater signal attenuation from EMI
  4. Reduced bend radius at the bundle center
Show answer & explanation

Correct answer: A - Heat buildup within the cable bundle

Question 10

On a job site, a requirement in the local building code directly conflicts with a recommendation in an ANSI/TIA standard. Which should the installer follow?

  1. The ANSI/TIA standard, as the industry best practice
  2. The local building code
  3. Whichever was published more recently
  4. The manufacturer's installation instructions
Show answer & explanation

Correct answer: B - The local building code